Kawaida | Kitengo | IEC/EN 61009-1 | |||||||
Umeme vipengele | Hali | Aina ya elektroniki | |||||||
Aina(aina ya mawimbi ya kuvuja kwa ardhi inahisiwa) | A,AC | ||||||||
Tabia ya kutolewa kwa thermo-magnatic | B,C | ||||||||
Imekadiriwa sasa katika | A | 6,10,16,20,25,32,40 | |||||||
Nguzo | P | 1P+N | |||||||
Ilipimwa voltage Ue | V | 110/220,120/240 | |||||||
Unyeti uliokadiriwa I△m | A | 0.01,0.03,0.1 | |||||||
Imekadiriwa uwezo wa kutengeneza na kuvunja mabaki I△m | A | 500 | |||||||
Imekadiriwa uwezo wa mzunguko mfupi wa Icn | A | 6000 | |||||||
Muda wa mapumziko chini ya I△m | s | ≤0.1 | |||||||
Ilipimwa mara kwa mara | Hz | 50/60 | |||||||
Msukumo uliokadiriwa kuhimili voltage(1.2/50)Uimp | V | 4000 | |||||||
Voltage ya mtihani wa dielectric katika ind.Freq.kwa dakika 1 | kV | 2 | |||||||
voltage ya insulation Ui | 500 | ||||||||
Kiwango cha uchafuzi wa mazingira | 2 | ||||||||
Mitambo vipengele | Maisha ya umeme | t | 4000 | ||||||
Maisha ya mitambo | t | 4000 | |||||||
Kiashiria cha nafasi ya mawasiliano | Ndiyo | ||||||||
Kiwango cha ulinzi | IP20 | ||||||||
Halijoto iliyoko (kwa wastani wa kila siku ≤35℃) | ℃ | -5~+40(Maombi maalum tafadhali rejelea marekebisho ya fidia ya halijoto) | |||||||
Halijoto ya kuhifadhi | ℃ | -25~+70℃ | |||||||
ufungaji | Aina ya uunganisho wa terminal | Upau wa basi aina ya kebo/Pini/Upau wa basi aina ya U | |||||||
Ukubwa wa terminal juu / chini kwa kebo | mm² | 16 | |||||||
AWG | 18-5 | ||||||||
Ukubwa wa terminal juu / chini kwa busbar | mm² | 16 | |||||||
AWG | 18-5 | ||||||||
Torque ya kukaza | N*m | 2 | |||||||
Katika-Ibs. | 18 | ||||||||
Uhusiano | Kutoka juu | ||||||||
Kuweka | Aina ya programu-jalizi |